Water Quality Results

Glenrowan - Full treatment 

Rolling Year Summary Results for Aug-2009 
 
Last Update Date Wednesday, 23 September 2009
 

Glenrowan Supply 

Bacteriological This Period   Rolling 12 Months
Limit Units # Samples % samples with no E.Coli Min Test Value Max Test Value   # Samples % samples with no E.Coli Comply Y/N Min Test Value Max Test Value
Escherichia Coli  98%=0 orgs/
100mL
.000    52  100.0% 
 
Physical This Period   Rolling 12 Months
Limit Units # Samples Mean Value Min Test Value Max Test Value   # Samples 95% UCL of the Mean Comply Y/N Min Test Value Max Test Value
Turbidity  5.0  NTU   .39  0.05  0.8    53  .58  0.05  6.5 
 
Chemicals or
By-Products of
Treatment/
Disinfection
This Period   Rolling 12 Months
Limit Units # Samples Mean Value Comply Y/N Min Test Value Max Test Value   # Samples Mean Value Min Test Value Max Test Value
Aluminium  0.2  mg/L   .040  0.04  0.04    13  .030  0.005  0.05 
Chloroacetic Acid  0.15  mg/L   .003  0.0025  0.0025    12  .003  0.0025  0.0025 
Dichloroacetic Acid  0.1  mg/L   .005  0.005  0.005    12  .010  0.005  0.015 
Trichloroacetic Acid  0.1  mg/L   .003  0.0025  0.0025    12  .009  0.0025  0.013 
Trihalomethanes  0.25  mg/L   .014  0.014  0.014    12  .036  0.014  0.071