Water Quality Results

Oxley - Full treatment 

Rolling Year Summary Results for Aug-2009 
 
Last Update Date Wednesday, 23 September 2009
 

Oxley Supply 

Bacteriological This Period   Rolling 12 Months
Limit Units # Samples % samples with no E.Coli Min Test Value Max Test Value   # Samples % samples with no E.Coli Comply Y/N Min Test Value Max Test Value
Escherichia Coli  98%=0 orgs/
100mL
.000    52  100.0% 
 
Physical This Period   Rolling 12 Months
Limit Units # Samples Mean Value Min Test Value Max Test Value   # Samples 95% UCL of the Mean Comply Y/N Min Test Value Max Test Value
Turbidity  5.0  NTU   .28  0.1  0.6    52  .38  0.05  2.2 
 
Chemicals or
By-Products of
Treatment/
Disinfection
This Period   Rolling 12 Months
Limit Units # Samples Mean Value Comply Y/N Min Test Value Max Test Value   # Samples Mean Value Min Test Value Max Test Value
Aluminium  0.2  mg/L   .010  0.01  0.01    13  .010  0.005  0.03 
Chloroacetic Acid  0.15  mg/L   .003  0.0025  0.0025    12  .003  0.0025  0.0025 
Dichloroacetic Acid  0.1  mg/L   .008  0.008  0.008    12  .009  0.005  0.016 
Trichloroacetic Acid  0.1  mg/L   .009  0.009  0.009    12  .010  0.006  0.019 
Trihalomethanes  0.25  mg/L   .016  0.016  0.016    12  .020  0.012  0.034