Water Quality Results

Springhurst - Full treatment 

Rolling Year Summary Results for Aug-2009 
 
Last Update Date Wednesday, 23 September 2009
 

Springhurst Supply 

Bacteriological This Period   Rolling 12 Months
Limit Units # Samples % samples with no E.Coli Min Test Value Max Test Value   # Samples % samples with no E.Coli Comply Y/N Min Test Value Max Test Value
Escherichia Coli  98%=0 orgs/
100mL
.000    53  100.0% 
 
Physical This Period   Rolling 12 Months
Limit Units # Samples Mean Value Min Test Value Max Test Value   # Samples 95% UCL of the Mean Comply Y/N Min Test Value Max Test Value
Turbidity  5.0  NTU   .28  0.1  0.7    53  .47  0.05  1.6 
 
Chemicals or
By-Products of
Treatment/
Disinfection
This Period   Rolling 12 Months
Limit Units # Samples Mean Value Comply Y/N Min Test Value Max Test Value   # Samples Mean Value Min Test Value Max Test Value
Aluminium  0.2  mg/L   .030  0.03  0.03    13  .047  0.005  0.25 
Chloroacetic Acid  0.15  mg/L   .003  0.0025  0.0025    12  .003  0.0025  0.0025 
Dichloroacetic Acid  0.1  mg/L   .031  0.031  0.031    12  .019  0.007  0.034 
Trichloroacetic Acid  0.1  mg/L   .033  0.033  0.033    12  .025  0.0025  0.045 
Trihalomethanes  0.25  mg/L   .100  0.1  0.1    12  .092  0.015  0.16